Home >Modem>Profinet>Profinet Gateway
PN1-S25 Profinet to Modbus gateway patch module Support ProfiNet to ModBus protocol TIA Portal/STEP 7 configuration

[Communication interface]:TTL

[Working voltage]:3.3V

[Product size]:24*19mm

[Product weight]:3±1g

[Introduction]:PN1-S25 wireless module is a Profinet to Modbus RTU gateway module designed for industrial communication. It is used to map Modbus data to Profinet. It uses GSD files for integration, and can read and write Modbus devices without code. Data can be quickly set and transferred to the PLC. All Modbus commands are loaded in the form of modules. The memory mapping relationship between Profinet and Modbus is intuitive and can be queried in STEP 7 or TIA Portal software. The status byte can be loaded to query the connection status of the Modbus device and monitor the device status in real time. It supports Modbus RTU (master/slave) protocol.

PIN
Serial number Pin silk screen describe
1 NC Dangling
2 TXD2 The serial port sends data, and the TTL level communication voltage only supports 3.3V
3 RXD2 The serial port receives data, and the TTL level communication voltage only supports 3.3V
4 RXD2_LED The output is flipped when serial port 2 receives data. The default output is high level. When receiving data, it outputs 25Hz square wave.
5 TX2_EN Serial port 2 sends indication pin, which is set high when the serial port sends data and low normally; this pin can be used as RS485 chip enable control pin
6 TXD2_LED The output of serial port 2 is flipped when there is data to send, the default output is high level, and the output is 25Hz square wave when receiving data
7 RXD1_LED The output flips when serial port 1 receives data. The default output is high level. When receiving data, it outputs 25Hz square wave.
8 TXD1_LED The output flips when serial port 1 has data to send, and the default output is high level. When receiving data, it outputs a 25Hz square wave
9 ERR_LED (Modbus) Communication error indication, pull low: Modbus communication abnormal; set high: Modbus communication normal; when the configuration software controls the flashing indicator light, the level flips at the same time as SYS
10 SYS_LED System (PN connection), pull low: PROFINET connection established, set high: PROFINET connection not established; when the configuration software controls the flashing indicator light, the level is flipped at the same time as ERR
11 NC Dangling
12 GND Common ground terminal, negative power input
13 GND Common ground terminal, negative power input
14 VCC Power positive input, supports 3.3V input
15 VCC Power positive input, supports 3.3V input
16 NC Dangling
17 NC Dangling
18 NRST By default, the internal pull-up is set to high, and the module will restart if the pull-down is set to low (about 100ms).
19 RELOAD The factory reset pin has an internal weak pull-up and can be connected to an external reset button. A low level of about 5 to 10 seconds can restore the factory settings; a low level of 0.5 to 2 seconds can restart the module; pull low in the power-off state and then power on, and the device enters the upgrade mode;
20 NC Dangling
21 LINK_LED 10M PHY indicator light, pulled low after successful PHY negotiation, flashes when data is being sent or received;
22 SPD_LED 100M PHY indicator light, pulled low after PHY negotiation is successful, flashes when data is being sent or received;
23 GND Common ground terminal, negative power input
24 GND Common ground terminal, negative power input
25 RX_N Ethernet receiving RX-signal
26 RX_P Ethernet receives RX+ signal
27 TX_N Ethernet sends TX-signal
28 TX_P Ethernet sends TX+ signal
29 NC Dangling
30 WDI Module working indication. This pin will continuously output square wave (1K-1MHZ) after the module is working normally.
31 TXD1 The serial port sends data, and the TTL level communication voltage only supports 3.3V
32 RXD1 The serial port receives data, and the TTL level communication voltage only supports 3.3V
33 NC Dangling
34 TX1_EN Serial port 1 sends indication pin, which is set high when the serial port sends data and low normally; this pin can be used as RS485 chip enable control pin
35 NC Dangling
36 GND Common ground terminal, negative power input