ME31-XDXX0400 4-way temperature acquisition module PT100 thermal resistor RS485 network port to Modbus K-type thermocouple

[Communication interface]:RJ45, RS485

[Working voltage]:DC 8~28V

[Installation method]:Guide rail/screw

[Introduction]:ME31-XDXX0400 is a PT100 thermal resistor temperature acquisition module with 4-channel PT100 temperature acquisition function, and supports the acquisition of 2/3-wire PT100 temperature sensors. It also has a display screen to facilitate customers to debug and configure on-site and view the temperature. This temperature acquisition module supports both network and RS485 communication interfaces, and supports Modbus TCP protocol or Modbus RTU protocol for acquisition. It can also be used as a Modbus gateway, automatically sending instructions from non-local Modbus addresses through the serial port/network port, supporting Modbus TCP and Modbus RTU protocol conversion, and convenient for expanding Modbus slave devices.

Category Name Parameters
power supplyWorking voltageDC8~28V
Power indicatorBlue LED indication
CommunicationCommunication interfaceRJ45, RS485
Baud rate1200~115200bps (default 9600)
Communication protocolStandard Modbus TCP, Modbus RTU protocol
MODBUSDevice addressCan be modified through Modbus command, host computer, device button
Temperature collectionNumber of channels4-way
Sensor type2, 3-wire PT100 temperature sensor
Temperature resolution0.1℃
AccuracyNormal temperature (25±5℃) condition: ±0.1%±1℃
Full temperature (-40~85℃) condition: ±0.5%±1℃
Collection frequency1Hz
Collection displayOLED screen display
otherProduct size121mm * 72mm * 34mm (length * width * height)
Product weight140 ±5 g
Working temperature and humidity-40 ~ +85℃, 5% ~ 95%RH (no condensation)
Installation methodGuide rail installation, screw installation


Category Name Parameters
Ethernet parametersWorking modeTCP server (up to 4 client accesses)
Local IP192.168.3.7
Local port502
Subnet mask255.255.255.0
Gateway address192.168.3.1
DHCPOff
Local MACDetermined by the chip (fixed)
Target IP192.168.3.3
Target port502
DNS server114.114.114.114
Active uploadOff
Serial port parametersBaud rate9600bps (8 types)
Check methodNone
Data bit8
Stop bit1
MODBUS ParametersModbus master-slaveSlave
Address1