MA01-XHXX0200-V2P 2AI Isolation type RS485 Control Serial port IO networking module Supports ModBus Protocol

[Specifications]:2AI

[Communication Interface]:RS485

[Operating Voltage]:DC 8~28V

[Mounting Method]:DIN Rail + Positioning Hole

[Size]:53.8*30*110mm

[Product Weight]:72.5±2g

[Introduction]:The MA01-XHXX differential analog input series is a high-precision differential analog input module based on the MODBUS RTU protocol, designed specifically for industrial automation, process control, and data acquisition systems. This series utilizes advanced differential signal input technology, effectively suppressing common-mode noise and significantly improving signal measurement accuracy and system reliability in complex electromagnetic environments. The product is coated with a conformal coating, providing protection against mold, moisture, and salt spray.

category name parameter
power supply Operating voltage

DC 8~28V

Operating current

≤150mA @12V

Power indicator

Green LED indicator

serial port Communication interface

RS485

baud rate

1200bps~115200 bps (default 9600 bps)

Data bits

8 (fixed)

Check bit

No parity, odd parity, even parity (default is no parity)

Stop bit

1 (fixed)

Communication Protocol

MODBUS RTU protocol

Device address

0~247 (default address 1, 0 is the broadcast address)

indicator lights

The red LED remains lit after power-on; during communication, it flashes with a 60ms cycle.

AI input AI approach

Routes 1/2/4/6/8/10/12

Input type

Differential input

Voltage measurement range

0-5V / 0-10V

Current measurement range

0-20mA / 4-20mA

Measurement accuracy

3‰

resolution

16-bit

sampling frequency

40Hz

Input impedance

260Ω

Filter parameters

1 to 16 (default 6)

other Product Dimensions

1/2 lanes: 53.8*30*110.0 mm

4/6-way: 90.0*40*116.5 mm

Routes 8/10/12: 116.5*40*90.0 mm

Product weight

1/2 route: 72.5±2g

4/6 route: 118.5±2g

Routes 8/10/12: 162.0±2g

Operating temperature and humidity

-40 to +85℃, 5% to 95%RH (non-condensing)

Storage temperature and humidity

-60 to +125°C, 5% to 95%RH (non-condensing)

Installation method

Guide rail and positioning hole installation