Home >Modem>Distributed IO>Ethernet/RS485 IO

M31-AXXXA000G 16DI M31 series distributed IO host supports Modbus TCP protocol and Modbus RTU protocol for acquisition control

[Communication interface]: RJ45, RS485

[Working voltage]:DC 9~36V

[Product weight]:180±5g

[Introduction]:The M31 series distributed IO host supports Modbus TCP protocol and Modbus RTU protocol for acquisition control. The device supports simultaneous access by 5 clients and supports function codes 01/02/03/04/05/06/15/16. The shell adopts three-proof coating, which is Anti-Fungal, Anti-Humidity, and Anti-Salt Spray. This saves costs and facilitates customers to access the current on-site environment; the modules are self-contained. With status diagnosis function, it can monitor the communication status of IO modules in real time; it can support a maximum of 16 IO expansion modules.

PIN
SymbolnameFunction Description
DI1Dll switch inputDll switch input interface, used in conjunction with COMA
DI2DI2 switch inputDI2 switch input interface, used in conjunction with COMA
DI3DI3 switch inputDI3 switch input interface, used in conjunction with COMA
DI4DI4 switch inputDI4 switch input interface, used in conjunction with COMA
COMADI switch input common terminalDI1-DI4 share the COMA common port
DI5DIS switch inputDI5 switch input interface, used in conjunction with COMB
DI6DI6 switch inputDI6 switch input interface, used in conjunction with COMB
DI7DI7 switch inputDI7 switch input interface, used in conjunction with COMB
DISDIS switch inputDI8 switch input interface, used in conjunction with COMB
COMBDI switch input common terminalDI5-DI8 share the COMB common terminal
DI9DI9 switch inputDI9 switch input interface, used in conjunction with COIC
DUODUO switch inputDI10 switch input interface, used in conjunction with CONIC
DIllDIll switch inputDIll switching input interface, used in conjunction with CONIC
DI12DI12 switch inputDI12 switch input interface, used in conjunction with CONIC
DI13DI13 switch inputDI13 switch input interface, used in conjunction with COMC
DI14DI 14 switch inputDI 14 switch input interface, used in conjunction with COMC
DI15DI15 switch inputDll 5 switch input interface, used in conjunction with COMC
DI16DI16 switch inputDI16 switch input interface, used in conjunction with COMC
COMCDI switch input common terminalDI9-DI16 share the COMC common terminal
ReloadFactory reset auto-negotiationPress and hold for 5-10 seconds to restore factor}- settings; double-click within 2 seconds to automatically negotiate the expansion module
A(RS485)RS485 A interfaceRS485 A interface
B(RS485)RS485 B interfaceRS485 B interface
G(RS485)RS485G interfaceRS485G interface
PEgroundground
V-(DC9-36V)Negative pole of power supplyDC (9-36V) power supply negative interface
V+ (DC9-36V)Positive pole of pcwer supplyDC (9-36V) power supply positive interface
LAN1Network portStandard RJ45 network cable interface