M31-AXXXA000G 16DI M31 series distributed IO host supports Modbus TCP protocol and Modbus RTU protocol for acquisition control

[Communication interface]: RJ45, RS485

[Working voltage]:DC 9~36V

[Product weight]:180±5g

[Introduction]:The M31 series distributed IO host supports Modbus TCP protocol and Modbus RTU protocol for acquisition control. The device supports simultaneous access by 5 clients and supports function codes 01/02/03/04/05/06/15/16. The shell adopts three-proof coating, which is Anti-Fungal, Anti-Humidity, and Anti-Salt Spray. This saves costs and facilitates customers to access the current on-site environment; the modules are self-contained. With status diagnosis function, it can monitor the communication status of IO modules in real time; it can support a maximum of 16 IO expansion modules.

CategoryNameParameter
power supplyOperating VoltageDC9 ~ 36V
Power indicatorPWK red LED indicator light
communicationCommunication interfaceRJ45, RS485
baud rate9600bps (optional)
ProtocolStandard Modbus TCP, Modbus RTU protocol
MODBUSDevice addressbe modified through Modbus instructions, host computer and hardware dialing
DI inputinput typeNPN,PNP
Input voltage12~24 V
Collection frequencyMaximum 2.5 Hz
Input instructionsDI green LED indicator light
AI inputCollection characteristicsSingle-ended input
input type0-20mA, 4-20mA
AI resolution3%
Collection frequencyMaximum 2.5 Hz
Input instructionsnone
DO outputDO output typeType A relay(Normally open)
DO output modeLevel output
Relay contact capacity5A 30VD,5A 250VAC (the maximum supported total current of the same COM common terminal is 8A)
Output instructionsDO green LED indicator light
otherProduct Size1 10 mm * 40 mm * 100 mm (length*width*height)
Working temperature and humidity‘-40~+85℃, 5%~95%RH (no condensation)
Storage temperature and humidity-40 ~ +105℃, 5% 〜95%RH (no condensation)
Installation methodInstallation of positioning holes and guide rails

Device default parameters

Category       NameParameter
Basic parametersModbus address1
baud rate9600bps (9 options available)
Check digitNone (default). Odd, Even
data bits8
Stop bit1
DI filter parameters6
AI filter parameters6
Network parametersOperating modeTCP server (up to 5 clients access)
DHCPclosure
Gateway address192.168.3.1
subnet mask255.255.255.0
Local IP192.168.3.7
native port502
Target IP192.168.3.3
target port502
DNS sen-er114.114.114.114
Native MACDetermined by chip (fixed)