Home >Modem>Distributed IO>Ethernet/RS485 IO
M31-AXXX8000G-U 8DI High-performance distributed I/O host Standard ModBus protocol ModBus TCP/RTU High response and high protection

[Specifications]: 8DI

[Communication Interfaces]:RJ45, RS485

[Operating Voltage]: DC 9~36V

[Installation Method]: Positioning hole, DIN rail mounting

[Size]:110*40*100mm

[Introduction]:
This high-performance distributed I/O host supports standard Modbus TCP and Modbus RTU protocols, suitable for data acquisition and control. The device is equipped with 10/100M adaptive dual Ethernet interfaces and supports switch functionality. The internal bus speed can reach up to 1ms. It features a reset function for both digital and analog outputs in case of network interruption, ensuring restoration to the preset state. The product casing is coated with a three-proof paint, providing anti-mildew, anti-moisture, and anti-salt spray functions.

category name Specifications
power supply Operating voltage DC 9~36V; with reverse polarity protection
Power indicator PWR red LED indicator
Power consumption 2~4W
communication Communication interface RJ45*2 (dual network ports), RS485
baud rate 9600bps (optional)
Communication Protocol Standard Modbus TCP, Modbus RTU protocols
Internal bus Up to 1ms
Modbus Device address Modification can be achieved via Modbus commands, host computer, and hardware DIP switches.
DI Input Input type NPN、PNP
Input range DC 10~28V
Isolation methods Each channel is individually opto-isolated.
Input impedance 7.2kΩ
sampling frequency 1000 Hz  
Counting frequency <500Hz
Filtering time Default time 6ms
Input Instructions DI green LED indicator
AI input Acquisition characteristics Differential input
Input type Differential current: 0-20mA, 4-20mA, ±20mA
AI resolution 16-bit (differential)
AI accuracy 1‰ (difference)
refresh rate Differential maximum 70Hz
Input Instructions AI Green LED Indicator
Relay-type DO output DO output type Type A relay (normally open)
DO output mode Level output, pulse output
Relay contact capacity 5A 30VDC, 5A 250VAC (maximum total current supported at the same COM common terminal is 8A)
Output Indicator DO green LED indicator
Transistor-type DO output DO output type PNP type
DO output mode Level output, pulse output
Output capability Supports output up to 0.5A per channel and 4A per COM port at voltages between 10 and 30V.
other Product Dimensions 110mm * 40mm * 100mm (Length * Width * Height)
Operating temperature and humidity -40 to +85℃, 5% to 95%RH (non-condensing)
Storage temperature and humidity -40 to +105℃, 5% to 95%RH (non-condensing)
Installation method Positioning holes and guide rail installation